OT security starts with the consequences in the plant
This article is an English adaptation of my German original on ot-cyber.de. Why IT segmentation is not enough in OT I often get called in when a plant is "already segmented". Most of the time that means IT ha
This article is an English adaptation of my German original on ot-cyber.de.
Why IT segmentation is not enough in OT
I often get called in when a plant is "already segmented". Most of the time that means IT has set up VLANs: one for the offices, one for production, maybe one for cameras. In between sits a firewall with a long rule set. On paper it looks clean.
Then I ask two questions. What is the worst thing that can happen in this hall? And in which zone is the controller that prevents exactly that? That is usually when the room goes quiet.
I'm Max Gilg, an OT cybersecurity consultant based in Rosenheim, Germany. What I tell my clients: if you don't know your consequences, you can't protect against them. Real OT security starts when every critical consequence is deliberately protected, and a segmentation that doesn't know the consequences is not safety-ready.
What does "defining consequences" mean?
In IT we think about data: confidentiality, integrity, availability. In a plant, the questions are different. A boiler that overheats. A dosing unit that feeds in too much. A robot that starts moving while someone is inside the cell. A line that stays down for three weeks because nobody can say for sure whether the controller is still clean.
Defining consequences means writing exactly this list, together with process engineering, maintenance and production. For each consequence we work out:
- Which controller, which signal, which access path could trigger it?
- How fast does it become dangerous?
- What protects against it today, and does that still work when the software is lying?
Idaho National Laboratory turned this into a method: Consequence-driven Cyber-informed Engineering (CCE). It runs in four phases. First the most severe possible events are prioritized, then the systems behind them are analyzed, then the attack paths are mapped from an attacker's point of view. Countermeasures only come at the end, and they are mainly engineering changes to the plant itself.
What's wrong with classic segmentation?
Nothing, really. It just answers a different question. An IT network is split by organization: department, site, device type. OT needs a split by impact.
I keep seeing the same three mistakes:
The safety system sits in the process network. The safety instrumented system (SIS) that trips on overpressure lives in the same segment as the regular PLC and the engineering workstation. Whoever reaches one reaches the other. In 2017 the Triton malware attacked exactly this kind of safety controller, Triconex controllers in a petrochemical plant (CISA report MAR-17-352-01, 18 December 2017).
The zone is too big. A whole hall is "one zone". It contains packaging, where an outage is annoying, and dosing, where an error puts people at risk. Both get the same rules.
Remote access cuts straight through. The access path for the machine vendor ends on a jump host that can see everything. One service laptop, and the nicest segmentation is bypassed.
What does consequence-driven segmentation look like?
IEC 62443-3-2 (2020 edition) describes the process: define the system under consideration, partition it into zones and conduits, assess the risk for every zone and conduit, and set the target security level (SL-T). According to the standard's table of contents, documenting the security requirements is part of it as well. The standard also has a dedicated requirement to separate safety-related assets from the rest (ZCR 3.3). With a finished consequence list this goes much faster, because half of the risk assessment is already done.
What does that mean on the shop floor? Everything that protects life and limb gets its own zone. Ideally there is no write access from outside, and programming only happens with a key switch on site. The rest I cut by severity: parts with the same consequence go together, areas with severe consequences get tighter boundaries.
For every connection between two zones you should be able to say in one sentence what it is for. If you can't, it gets blocked. And every critical consequence also gets a protection that works without software: a relief valve, a mechanical limit switch or a hardwired emergency stop. That still works when the segmentation fails.
In the SANS Five ICS Cybersecurity Critical Controls, this is Control 2, Defensible Architecture. I can only defend what I know.
A fictional example: a dairy
The following example is made up, but typical for many plants in my region. Picture a mid-sized cheese dairy in the Chiemgau area of Bavaria with one production hall. IT has set up a VLAN called "Production". On it: the ammonia refrigeration system with its safety controller, the milk pasteurizer, the CIP cleaning system, the packaging line, the engineering PC and the remote access router of the packaging vendor. The service technician comes in via VPN into that VLAN and can therefore also see the refrigeration controls. He never needed them.
In a workshop, plant management, maintenance, quality assurance and IT would write this consequence list in one morning:
| Consequence | Who is affected | Protection without software | Zone |
|---|---|---|---|
| Ammonia leaks from the refrigeration system | People | Relief valve, hardwired gas detection | Safety |
| Milk is not heated enough | Consumers, recall | Divert valve, fails to return when de-energized | Safety |
| Caustic gets into the product line | People, consumers | Double-seat valve with leakage chamber | Process |
| Wastewater too acidic going into the sewer | Environment | pH limit switch blocks the discharge pump | Process |
| Packaging line stops | Delivery time | Not needed, plan the restart | Packaging |
After that, the split almost explains itself. The refrigeration safety chain, the gas detection system and the pasteurizer's divert valve go into their own Safety zone. The divert valve fails to the return position when it loses power: if the milk isn't hot enough, it flows back, no matter what the controller reports. Pasteurizer, CIP and refrigeration control form the Process zone. Packaging gets its own zone with lower protection needs.
The packaging vendor's remote access now ends on a jump host that only leads into the Packaging zone, is time-limited and gets approved by the shift supervisor. Between Safety and Process there is only a read-only conduit. The effort in this example: one workshop, one additional firewall between the zones and new rules for remote access. The switches stay where they are.
What does this mean for machine builders?
From 20 January 2027, the EU Machinery Regulation (EU) 2023/1230 applies. Annex III, section 1.1.9 "Protection against corruption" requires: "The machinery or related product shall be designed and constructed so that the connection to it of another device, via any feature of the connected device itself or via any remote device that communicates with the machinery or related product does not lead to a hazardous situation." It continues: "Software and data that are critical for the compliance of the machinery or related product with the relevant essential health and safety requirements shall be identified as such and shall be adequately protected against accidental or intentional corruption."
Section 1.2.1 requires control systems to withstand "intended and unintended external influences, including reasonably foreseeable malicious attempts from third parties leading to a hazardous situation" (Regulation (EU) 2023/1230, Annex III). On top of that comes the Cyber Resilience Act for products with digital elements.
Whoever builds a machine knows its hazardous consequences best. That list belongs in the risk assessment, and the machine's security architecture should build on it. An emergency stop that only works through software will sooner or later become a discussion point at the customer's acceptance test.
Buyers on the operator side can put exactly this into their tender documents: "Provide a list of the safety-critical consequences and show how each of them is protected without software."
How do I get started?
With half a day and the right people in the room: production, maintenance, process engineering, IT. Write down the five consequences that must never happen. For each one, trace the path from the consequence back to the network. By then at the latest you will see whether your segmentation actually protects or just looks tidy.
If you want to see what a consequence means in a real incident, you can play through it in our free OT emergency drills in the browser, no login, for example on a cheese dairy. We support operators and machine builders in Germany, Austria and Switzerland with implementing IEC 62443-3-2/3-3 in production and with the security architecture of machines.
Original (German): https://ot-cyber.de/blog/ot-security-beginnt-bei-den-folgen-in-der-anlage.html
Max Gilg is an OT cybersecurity consultant based in Rosenheim, Germany (OT-Cyber.de).
Originally published by Dev.to Security. Aggregated on AIWithGhost for educational purposes — full credit and traffic to the original publisher.